Short definition
Lighting the pilot on a standing-pilot gas water heater is a sequence printed on the appliance itself: gas valve to PILOT, depress and hold the pilot button, ignite with the piezo or a long match, hold 30–60 seconds for the thermocouple to warm, release, then turn the valve to ON. The single most important rule: do not attempt ignition if you can smell gas.
What it is
A standing-pilot gas water heater keeps a small flame burning continuously next to a thermocouple — a sensor that produces a tiny electrical signal when heated. That signal holds open a safety valve in the gas-control body. When the burner needs to fire, gas flows past the still-lit pilot, ignites, and heats the tank.
If the pilot goes out — wind through the draft hood, dust on the orifice, an aging thermocouple — the safety valve closes. No pilot, no burner, no hot water. Relighting is the homeowner reset.
The procedure is manufacturer-specific and printed on a placard on the front of the heater. Bradford White, Rheem, A.O. Smith, and the rest all use the same general sequence with small variations. Read the placard.
Modern units (post-2003 FVIR-listed) have a sealed combustion chamber with a flame arrestor screen and a piezo igniter — no match required. Older units may need a long match through a viewport. Tankless and electronic-ignition tank heaters do not have a homeowner pilot procedure; they re-ignite automatically and show error codes when they can’t.
Why it matters to a homeowner
A pilot relight is a 5-minute homeowner job in the 90% case. A pilot that won’t stay lit after relight is usually a thermocouple — a $15 part, $80–$150 service call. There’s no reason to wait two days for a plumber if you understand the rule and the procedure.
The rule is short: never attempt ignition if you can smell gas. Wait for the smell to clear. If it doesn’t clear in a few minutes with the gas valve in OFF, leave the house and call the utility. Lighting a flame in a room with detectable gas is the worst-outcome version of this task.
When you’ll encounter this term
- Brand-new water heater install — first ignition takes longer than a relight because the gas line still has air in it
- Returning from vacation where gas was shut off
- Pilot blown out during a windstorm — relight, but if it blows again within hours, address combustion-air drafting
- Recurring pilot outage after relight — the thermocouple is the most likely culprit
The procedure (general — read your placard)
- Smell first. Kneel down and smell near the floor for 60 seconds. Gas is heavier than air on propane systems, lighter than air on natural gas — but mercaptan accumulates near the appliance regardless. If you smell anything, stop. Do not proceed.
- Turn the gas valve to OFF, wait at least 5 minutes for any residual gas to clear.
- Turn the gas valve to PILOT.
- Depress and hold the pilot button. This manually feeds gas to the pilot orifice only.
- Press the piezo igniter (or insert a long match through the viewport).
- Once the pilot lights, keep holding the pilot button for 30–60 seconds. The thermocouple needs to warm and energize the safety valve.
- Release the button. If the pilot stays lit, turn the gas valve to ON. Burner will fire when the thermostat calls for heat.
- If the pilot goes out when you release, repeat. On a brand-new install, repeat several times — air bleeds through the orifice over multiple attempts.
Common reasons a pilot won’t stay lit
- Thermocouple failure. Most common. $15 part, $80–$150 to replace.
- Flame-arrestor screen blocked by dust or lint on FVIR units. Vacuum the screen; if persistent, full clean-out service.
- Gas valve magnet failed. Replace the gas valve assembly.
- Gas pressure too low. Utility issue or partially closed shutoff upstream.
- Drafty utility room blowing the pilot out. Address combustion-air supply.
- Air still in line on a new install. Keep relighting; air bleeds out.
When to stop and call
- If the pilot won’t ignite after 2–3 attempts and there’s no smell of gas, the thermocouple is likely failed. Service call.
- If you smell gas at any point, stop. Wait for the smell to clear with the valve OFF, or leave and call the utility.
- If the unit has been involved in a flood or earthquake, gas-line integrity is unknown — do not relight. A pro pressure-tests the system first.
- If the unit is electronic-ignition (no continuous pilot, just a “click-click” at startup) and won’t fire, there is no homeowner relight procedure. Check the error code, then service call.
Common variants
- Standing pilot — the procedure above. Continuous flame; thermocouple-monitored.
- Electronic ignition — newer water heaters. No standing pilot. The unit sparks on demand. No homeowner pilot procedure; troubleshoot via error code.
- Hot-surface ignition — rare in residential water heaters; common in furnaces.
- Tankless — almost universally electronic ignition. Lighting the pilot doesn’t apply.
Related terms
- Pilot light — the broader concept
- Thermocouple — the part that fails most often
- Gas water heater — parent appliance
- Gas leak hazard — must rule out before any ignition